HD2134P.2 | micro manometer-thermometer for pitot tubes with data logger

Product.Nr.: HD2134P.2

Manufacturer: Senseca (ehemals DeltaOhm)

EUR 684,00
incl. 19 % VAT

  • delivery time bzw. Fertigungszeit variiert - bitte erfragen!
 
  • HD21x4P | micro manometer-thermometer for pitot tubes: HD2134P.2 | manometer with data logger


product description

measurement of air flow, differential pressure and temperature
 

features:

HD2114P.0 and HD2114P.2, HD2134P.0 and HD2134P.2 are portable micro manometers for pitot tubes with large LCD display. They are used to perform measurements in air conditioning, heating and ventilation.
They measure the differential pressure aquired by the pitot tube connected to the inputs of the instrument and achieve the airflow speed in ducts or vents; they also measure the temperature with thermocouple K probes.
The instruments can be used as thermometers and can be employed with any kind of thermocouple K sensor if a standard miniature connector is used.
The HD2114P.2 and HD2134P.2 instruments are data loggers. They store up to 36,000 samples which can be transferred from the instrument to a PC connected via the RS232C and USB 2.0 serial ports. The storing interval, printing and baud rate can be configured using the menu. They are also equipped with an RS232C serial port which can transfer in real time the acquired measurements to a PC or to a portable printer.


specifications:

measuring range: differential pressure: ±200 mbar
speed: 2 to 180 m/s
temperature: type K: -200 to +600°C, pitot tube: -200 to +600°C
max. over pressure: ±1 bar
resolution: differential pressure: 0.01 mbar - 1 Pa
speed: 0.5 m/s - 1 km/h - 1 ft/min - 1 mph - 1 knots
flow rate: 1l/s - 0.01·10 m/h - 0.01·10³ cfm
temperature: 0.1°C
accuracy: differential pressure: ±0.3 % f.s.
speed: ±(2 % reading +0.3 m/s)
temperature: ±0.1°C
storage of measured values: type: 2,000 pages containing18 samples each
quantity: 36,000 samples
storage interval: 1, 5, 10, 15, 30 s; 1, 2, 5, 10, 15, 20, 30 min; 1 h


Set consists of device HD2114P.2 with 20 mbar full scale and thermocouple type K input K, 4 1,5 V alkaline batteries, instruction manual, case and DeltaLog9 software. Pitot tubes have to be ordered separately!